Clark Reliance — Boiler Controls
Reliable Control of Alarms, Fuel Cut-Outs, Pumps — Pressures to 1800 PSI · New: REA100F Series

Physical Data
The REA100F-1000 represents a major step forward in boiler level switch reliability. Its robust dual-magnet design with positive interlock provides dependable operation in demanding high-pressure boiler applications — with zero dependence on electrical power to maintain switch position.
Maximum Operating Conditions
Max Pressure (MAWP)
1000 PSI (69 Bar)
Max Temperature
546°F (285°C)
Process Connection
1" FSW / 1" FNPT
Conduit Connection
3/4"
How It Works
A stainless steel float attached to a rod containing an encapsulated magnet pivots vertically within the chamber, driving a secondary magnet inside the switch housing. Repelling magnetic fields create a positive interlocking mechanism that is resistant to vibration and thermal effects. As liquid level drops, the float moves downward, shifting the magnets to activate the switch — configurable to open or close on rising or falling level.
Key Features
Microswitch Ratings
| Switch Type | SPDT |
| Approvals | UL, CE, CSA |
| AC Rating | 11A @ 125/250 VAC |
| DC Rating | 5A @ 30 VDC |
| DC (High Voltage) | ½A @ 125 VDC |
Enclosure & Approvals
| Hazardous Area | FM / CSA / ATEX / IECEx XP |
| NEMA Rating | NEMA 4X |
| IP Rating | IP66 / IP68 |
| UL | UL 60730 Approved |
| CRN | 0H16066 — All Provinces |
Electrical Ratings
| AC General Use | 0.75A @ 120/240 VAC |
| DC General Use | 1.00A @ 28 VDC |
| Endurance | 100,000 Cycles |
| Max Ambient Temp | 131°F (55°C) |
| Environment | Indoor or Outdoor |
Typical Applications

REA100F vs. EA100D — Piping Change Diagram
Pressures to 1800 WSP (124 Bar) · Dual Functions on Boilers & Tanks

Series EA101 models provide reliable and instant response. Probes respond to the rise and fall of water at pre-determined points, to actuate a variety of controls. Each Levalarm monitors up to 3-inch level variation. Multiple units, in series, extend the monitoring range. Recommended control for power plants and processing facilities.
Pressures to 800 psi (55 Bar) · No Pipe Modifications Required

For applications with EA100D, EA100S, or EA100SW legacy switches, the Retropak delivers a more reliable switch with less maintenance. The new access cover plate and probe is swapped out with the old float internals to create a dependable switch without requiring pipe modifications.
Tri-Magnet Technology · Pressures to 1000 PSI · UL 353 · FM 7710 Approved


Tri-Magnet Mechanism
Levalarm® Gold utilizes an advanced Tri-Magnet mechanism that provides the most secure switch action available for boiler low water alarms, switches, and cutouts. The unique magnetic design eliminates the effects of heat and vibration while delivering highly reliable level detection.
Tri-Magnet Switch Operation
A stainless steel float is attached to the end of a rod containing a stainless steel encapsulated magnet. The magnet travels vertically inside the pressure tube. The primary magnet on the float rod drives a secondary magnet, which in turn drives a tertiary magnet mounted to the switch arm to activate the switch mechanism.
As liquid level falls, the float drops and directs the magnets into the opposite position, causing the switch to change state. The use of repelling magnetic fields creates a positive interlocking switch that is unaffected by heat and maintains positive operation over long service periods.
Key Features
Three Models — Dimensions & Weights
| Model | A — Actuation | B — Connections | C — Height | D — Width | Weight |
|---|---|---|---|---|---|
| EA100G-150 | 6.08" (155 mm) | 6.41" (163 mm) | 16.87" (428 mm) | 9.00" (229 mm) | 46 lb (20.8 kg) |
| EA100G-300 | 6.00" (152 mm) | 6.51" (165 mm) | 17.40" (442 mm) | 10.00" (254 mm) | 65 lb (29.5 kg) |
| EA100G-600 | 7.51" (191 mm) | 8.35" (212 mm) | 21.00" (533 mm) | 13.00" (330 mm) | 157 lb (71.2 kg) |
Pressure Ratings (MAWP)
| EA100G-150 | 200 PSI (13.8 Bar) |
| EA100G-300 / 300SW | 500 PSI (34.5 Bar) |
| EA100G-600 / 600SW | 1000 PSI (69 Bar) |
Connection Sizes
| EA100G-150 | 1" FNPT |
| EA100G-300 | 1" FNPT / 1" FSW |
| EA100G-300SW | 1" FNPT / 1" FSW |
| EA100G-600 | 1" FNPT / 1" FSW |
| EA100G-600SW | 1" FNPT / 1" FSW |
Float Switch Ratings
| Switch Type | UL Listed / CSA Approved SPDT |
| UL Code | 35 |
| AC Rating | 5A @ 125, 250, or 480 VAC |
| DC Rating (125V) | ½A @ 125 VDC |
| DC Rating (250V) | ¼A @ 250 VDC |
| Max Switch Temp | 400°F |
Agency Approvals
Typical Applications
The EA100D and EA100S have been replaced by the EA100G (Levalarm Gold) series. NCI stocks the EA100D and EA100S for replacement applications.
| Model | Functions | Material | Connections | Max Pressure | Switch Rating | Status |
|---|---|---|---|---|---|---|
| REA100F-1000 | High or Low Alarm, Fuel Cut-Out | Cast Steel ASTM A216 Gr. WCB | 1" FNPT / 1" FSW | 1000 PSI | SPDT 11A @ 125/250 VAC | NEW |
| EA100G-150 | High or Low Alarm, Fuel Cut-Out | Cast Steel ASTM A216 Gr. WCB | 1" FNPT / 1" FSW | 200 PSI | UL/CSA SPDT 5A @ 125/250/480 VAC | ACTIVE |
| EA100G-300 / 300SW | High or Low Alarm, Fuel Cut-Out | Cast Steel ASTM A216 Gr. WCB | 1" FNPT / 1" FSW | 500 PSI | UL/CSA SPDT 5A @ 125/250/480 VAC | ACTIVE |
| EA100G-600 / 600SW | High or Low Alarm, Fuel Cut-Out | Cast Steel ASTM A216 Gr. WCB | 1" FNPT / 1" FSW | 1000 PSI | UL/CSA SPDT 5A @ 125/250/480 VAC | ACTIVE |
| EA100D | High or Low Alarm, Fuel Cut-Out | Cast Steel ASTM A216 Gr. WCB | 1" Screwed | 350 PSI | UL/CSA SPDT 5A @ 125/250/480 VAC | NOW OBSOLETE |
| EA100S | High or Low Alarm, Fuel Cut-Out | Cast Steel ASTM A216 Gr. WCB | 1" Screwed or S.W. | 800 PSI @ 520°F | UL/CSA SPDT 5A @ 125/250/480 VAC | NOW OBSOLETE |
| EA100 EPS | High or Low Alarm, Fuel Cut-Out | Cast Steel ASTM A216 Gr. WCB | 1" Screwed | 800 PSI @ 520°F | UL/CSA SPDT 5A @ 125/250/480 VAC | NOW OBSOLETE |
| EA101D | High/Low Alarm, Fuel Cut-Out & Pump Controls | Cast Steel ASTM A216 Gr. WCB | 1" Screwed | 350 WSP / 1000 PSI | Series R100L (plug-in) 5A @ 120/240 VAC | ACTIVE |
| EA101S | High/Low Alarm, Fuel Cut-Out & Pump Controls | Cast Steel ASTM A216 Gr. WCB | 1" Screwed or S.W. | 450 WSP / 1800 PSI | Series R100L (plug-in) 5A @ 120/240 VAC | ACTIVE |
| EA15R | Fuel Cut-Out or Fuel Cut-Out & Low Alarm | Bronze ASTM B61 | ¾" Screwed | 450 WSP | Series R100L (plug-in) 5A @ 120/240 VAC | ACTIVE |
| EA17 / EA18 Retropak PC | High/Low Alarm, Fuel Cut-Out & Pump Controls | Carbon Steel ASTM A516 | Flanged Cap | 250 WSP | — | ACTIVE |
** Applications: Boilers, Tanks & Water Columns | NCI stocks EA100D and EA100S for replacement service
Boilers & Tanks · Max 350 PSI · FM & CSA Approved · Replaced by EA100G Series

Key Specs
When tank or boiler levels reach predetermined high or low levels, the Levalarm EA100D will actuate bells, horns, or lights. EA100D models are also used for fuel cut-out control. The EA100D can be purchased with or without the body as Model EA100DLB.
How It Works
A stainless steel float swings at the end of a pivot rod. The rod head carries an Alnico V magnet. The magnet attracts one leg of a U-shaped armature which is attached to a microswitch leaf actuator. A buoyed float holds the switch open or closed, depending on terminals used. As liquid levels fall, the float drops and directs the magnet to the opposite position. A closed switch actuates alarms; an open switch achieves fuel cut-out.
Operation is highly reliable and sensitive because the magnet counterbalances the float, allowing accurate use of the float's buoyancy. The magnet does not "slide," eliminating any friction that could impede movement and accuracy.
Features & Options
Retropak Upgrade Available — Model EA100DRPT
Convert your EA100D float-style level alarm into a probe-style control station without disturbing any boiler piping. Fits EA100 and EA100D models. Installs on boilers, tanks, and water columns — pressures to 800 PSI.
Kit includes: flange cover with T-probe, probe housing kit with ½" conduit connection, replacement flange gasket, 30 ft. 18-gauge Teflon® insulated wire. Relay control sold separately.
Boilers & Tanks · Max 800 PSI @ 520°F · FM & CSA Approved · Replaced by EA100G Series

Key Specs
When tank or boiler levels reach predetermined high or low levels, the Levalarm EA100S will actuate bells, horns, or lights. EA100S models are also used for fuel cut-out control. The EA100S can be purchased with or without the body as Model EA100SLB. The EA100S handles higher pressures than the EA100D — rated to 800 PSI at 520°F.
How It Works
A stainless steel float swings at the end of a pivot rod. The rod head carries an Alnico V magnet. The magnet attracts one leg of a U-shaped armature which is attached to a microswitch leaf actuator. A buoyed float holds the switch open or closed, depending on terminals used. As liquid levels fall, the float drops and directs the magnet to the opposite position. A closed switch actuates alarms; an open switch achieves fuel cut-out.
Features & Options
Explosion-Proof Variant — Model EA100EPS
The EA100EPS is equipped with a switch housing that meets UL requirements for Class 1, Group D, Division 1 service. In design, materials, and performance, this model is similar to the EA100S. Explosion-proof models are ideally suited for chemical and petroleum field applications.
Retropak Upgrade Available — Model EA100SRPV
Convert your EA100S float-style level alarm into a probe-style control station without disturbing any boiler piping. Fits EA100S and EA100SW models. Installs on boilers, tanks, and water columns — pressures to 800 PSI.
Kit includes: flange cover with V-probe, probe housing kit with ½" conduit connection, replacement flange gasket, 30 ft. 18-gauge Teflon® insulated wire. Relay control sold separately.
Levalarm Sales & Application Support
Contact us for model selection, replacement parts, and Retropak retrofit quotes.
Quick RFQ