HomeAnderson SeparatorsFilter ElementsNatural Gas
Anderson / Clark-Reliance · Purity Products Group

Natural Gas Filter Elements

Anderson provides both liquid and solids removal for critical-use natural gas applications. Elements are available for coalescing (aerosol and liquid removal) and particle filtration, with series specified by major OEMs for power generation turbines. All elements are manufactured by Clark-Reliance's Purity Products Group.

Available Element Series

2710-Series — Fuel Gas Coalescing Elements

OEM Specified

When gas must be absolutely clean and dry — free from particulates, liquids, and entrained oils — the 2710-Series protects critical process applications for increased reliability and overall performance. Co-pleated microglass and synthetic media with a perforated stainless steel outer jacket. OEM-specified for gas turbine inlet and fuel gas systems.

Model Code2710 E 1 V *Example: 2710E1V-001 (with special field)

Operating Conditions

Flow DirectionInside → Out
Change-Out Differential15 PSID
Max Operating Temp400°F
Max Intermittent Temp450°F

Media & Construction

Media TypeCo-pleated microglass & synthetics
Cap MaterialStainless Steel
Outer JacketPerforated Stainless Steel Sheet
End Cap ConfigDouble Open Ended (DOE)
Seal MaterialFKM

Removal Efficiencies

Solid Removal0.3 µm @ 99.75%
Liquid Removal0.3 µm @ 99.9%

Dimensions — E Series

FieldOptions
E1ID 11.000" · OD 15.750" · Length 24.63"
E2ID 4.250" · OD 8.750" · Length 20.00"
E3ID 11.000" · OD 15.750" · Length 24.38"

Dimensions — H Series

FieldOptions
H2ID 11.000" · OD 15.750" · Length 24.63"
H4ID 8.875" · OD 12.500" · Length 24.50"
H5ID 8.875" · OD 12.500" · Length 24.50"
H6ID 11.000" · OD 15.750" · Length 24.63"
H7ID 11.000" · OD 17.500" · Length 36.25"
H9ID 4.250" · OD 7.750" · Length 36.50"

Seal Type Options

V — Flat sealVO — O-ring seal

ACR-836 — Gas Coalescing Elements (Large Diameter)

Protect critical natural gas process applications for increased reliability and overall performance. Designed to optimize particle retention, aerosol coalescence, and drainage with low pressure drop. Removal efficiency rating based on ANSI/CAGI 400 testing protocol. Co-pleated microglass and fiberglass media with aramid felt drain sleeve.

Model CodeACR 8 36 - 003 - H V *Example: ACR-836-003-V-001 (with special field)

Operating Conditions

Flow DirectionInside → Out
Change-Out Differential15 PSID
Maximum Differential75 PSID
Max Temperature400°F

Media & Construction

Media TypeCo-pleated Microglass & Fiberglass
Drain LayerAramid Felt Sleeve
Cap & Core MaterialCarbon Steel
Outside Diameter8 = 7.750"
Nominal Length36 = 36.63"

Configuration Options

FieldOptions
Micron Rating003 = 0.3 µm
Application NoteH = High Temperature
Seal MaterialB = Buna · V = FKM

ACR-Series — Gas Coalescing Elements (Standard)

Protect critical process applications for increased reliability and overall performance. Designed to optimize particle retention, aerosol coalescence, and drainage with low pressure drop. Removal efficiency rating based on ANSI/CAGI 400 testing protocol. Pleated microglass media with polyester felt drain sleeve.

Model CodeACR 4 36 - 003 - B CE *Example: ACR-436-003-BCE-001 (with special field)

Operating Conditions

Flow DirectionInside → Out
Change-Out Differential15 PSID
Maximum Differential50 PSID
Max Temp (Buna)250°F
Max Temp (Viton/FKM)275°F

Media & Construction

Media TypePleated Microglass
Drain LayerPolyester Felt Sleeve
Cap & Core MaterialPlated Steel

Configuration Options

FieldOptions
Outside Diameter3 = 3.775" · 4 = 4.563" · 5 = 5.625" · 6 = 6.000"
Nominal Length16 = 16.00" · 18 = 18.00" · 19 = 19.00" · 24 = 24.00" · 30 = 30.00" · 36 = 36.00"
Micron Rating003 = 0.3 µm
Seal MaterialB = Buna · G = Gylon · T = PTFE · V = FKM
Cap ConfigurationBlank = DOE · CE = SOE w/ Bolt Hole · CP = SOE w/ Post · SS = 304 SS Caps/Cores

CRSF-836 — Gas Particle Filter Elements

Absolute particle retention delivers the lowest single-pass particle counts, differential pressure, and reduced flush times. Premium pleated microglass media maximizes surface area for greater dirt-holding capacity, longer service life, and reduced cost of ownership. For natural gas applications where solid contaminant removal is the primary requirement.

Model CodeCRSF 8 36 - 01 - V *Example: CRSF-836-01-V-001 (with special field)

Operating Conditions

Flow DirectionOutside → In
Change-Out Differential15 PSID
Maximum Differential75 PSID
Maximum Temperature275°F

Media & Construction

Media TypePleated Microglass
Cap & Core MaterialCarbon Steel
Outside Diameter8 = 7.750"
Nominal Length36 = 36.00"
Cap ConfigurationDOE (standard)

Configuration Options

FieldOptions
Micron Rating01 = 1 µm · 03 = 3 µm
Seal MaterialV = FKM

Need help selecting the right element?

Call 1-201-419-6111 or email [email protected]