These units can eliminate resistance or bayonet
heaters and containment vessels. The straight through in-line
design minimizes clogging. The Ketema Schutte and Koerting Fig. 340 heaters have a low initial
cost, no moving parts, are easy to install and require little
or no maintenance.
The Ketema Schutte and Koerting Type 340 Heater, available in three sizes,
operates with maximum steam pressure of 180 psig, and a water
rate from 15 to 400 gpm. Maximum inlet water temperature is
150 °F, and maximum temperature
rise is also 150°F. Steam pressure should be at least 5 psi
greater than inlet water pressure.
Shown above is a nomograph
for determining the capacity, steam pressure, and steam
consumption of a 2" heater. The table of capacity factors,
Capacities
Table, simplifies size selection for other flow rates.
For inlet water temperatures exceeding 70°F, requirements decrease approximately 2% for each 20°F (up to 150 ° F); increase 2% for each 20°F under 70°F inlet water temperature.
The following example explains the use of Curve H: What heater size, steam pressure and rate are required to heat 320 gpm of water at 60 psig from 70° F to 100° F ?
Since discharge capacity (flow rate, gpm) is off curve, refer to Table 10 and divide 320 by 2.3 capacity factor. Locate 139 gpm on discharge capacity scale and project vertically up to the intersection with the 30 °F temperature rise line. From this point, project horizontally across to 60 psig inlet water pressure curve and vertically down to steam pressure of 75 psig. Return to horizontal projection and across to steam rate of 1,750 pph. Final answer is 2.3 times this figure, or 4,025 pph of steam at 75 psig using a 3" heater size. |