Dwyer Series 3000MR-3000MRS
Photohelic® Switch/Gages
|
| Combines
differential pressure gage with low/high set points. |
| |
|
Using solid
state technology, the Series 3000MR and 3000MRS Photohelic® switch/gages
combine the functions of a precise, highly repeatable differential
pressure switch with a large easy-to-read analog pressure
gage employing the durable, time-proven Magnehelic® design.
Switch setting is easy to adjust with large external knobs
on the gage face. Gage reading is unaffected by switch operation
- will indicate accurately even if power is interrupted.
Solid state design now results in greatly reduced size and
weight. Units can be flush mounted in 4-13/16" (122 mm) hole
or surface mounted with hardware supplied. 3000MR models
employ versatile electromechanical relays with gold over
silver contacts - ideal for dry circuits. For applications
requiring high cycle rates, choose 3000MRS models with SPST
(N.O.) solid state relays. All models provide both low and
high limit control and include 18-inch (45 cm) cable assemblies
for electrical connections. Dimensional Information
Gage accuracy is ±2% of full scale
and switch repeatability is ±1%. Switch deadband is
one pointer width - less than 1% of full scale. Compatible
with air and other non-combustible, non-corrosive gases,
they can be used in systems with pressures to 25 psig (1.725
bar). Optional construction is available for use to either
35 psig (2.42 bar) or 80 psig (5.51 bar).
Included Accessories:
Mounting ring, snap ring
18" (45 cm) cable assembly
(2) 3/16" tubing to 1/8" NPT adapters
(2) 1/8 " NPT pipe plugs
(4) 6-32 x 1-1/4" RH machine screws
(panel mounting)
(3) 6-32 x 5/16" RH machine screws
(surface mounting)
|
| |
| SPECIFICATIONS |
GAGE SPECIFICATIONS
Service: Air and non-combustible, compatible gases.
Wetted Materials: Consult factory.
Accuracy: ±2% of full scale at 70°F
(21.1°C). ±3% on -0 and ± on -00
models.
Pressure Limits: -20" Hg to 25 psig (-0.677 bar to 1.72 bar). MP option;
35 psig (2.41 bar), HP option; 80 psig (5.52 bar).
Temperature Limits: 20 to 120°F. (-6.67 to 48.9°C).
Process Connections: 1/8 female NPT (duplicated side and back).
Size: 4" (101.6 mm) dial face, 5" (127 mm) O.D. x 3-1/8" (79.38 mm).
Weight: 1.8 lb (816 g). |
| |
| SWITCH SPECIFICATIONS 3000MR |
Switch Type: Each setpoint has a 1 Form C relay (SPDT).
Relay Contacts: (resistive load) 1 Form C
rated 1.0A @ 30 VDC, 0.3A @ 110 VDC or 0.5A @ 125
VAC. Gold over clad silver - suitable for dry circuits.
Electrical Connections: 18" (46 cm) cable assembly with 8 conductors.
Optional lengths to 100´ (30.5 m).
Power Requirements: 24 VDC, regulated ±10%.
Mounting Orientation: Diaphragm in vertical position. Consult factory
for other position orientations.
Set Point Adjustment: Adjustable knobs on face.
Agency Approvals: CE. |
| |
| SWITCH SPECIFICATIONS 3000MRS |
Switch Type: Each setpoint has a solid state relay.
Switching Voltage: 20-280 VAC (47 - 63 Hz).
Switching Current: 1.0 amp (AC) max., 0.01
mA (AC) min., (2) SPST N.O.
Electrical Connections: 18" (46 cm) cable
assembly with 6 conductors, Optional lengths to 100´ (30.5
m).
Power Requirements: 24 VDC, regulated ±10%.
Mounting Orientation: Diaphragm in vertical position. Consult factory
for other position orientations.
Set Point Adjustment: Adjustable knobs on face.
Agency Approvals: CE. |
| |
| Accessories |
Mounting ring, snap ring
18" (45 cm) cable assembly
(2) 3/16" tubing to 1/8" NPT
(2) 1/8" NPT pipe plugs
(4) 6-32 x 1 ¼" RH machine screws (panel mounting)
(3) 6-32 X 5/16" RH machine screws (surface mounting) |
| |
| OPTIONS - ACCESSORIES |
|
OPTIONS
-TAMP Tamper-Proof Knobs, require special spanner-type key (included)
to adjust set points.
-LT Low Temperature Option for use under 20°F (-6.7°C).
-MP Medium Pressure increases maximum rated pressure to 35 psig (2.41
bar).
-HP High Pressure increases maximum rated pressure to 80 psig (5.5 bar).
ACCESSORIES
A-298 Flat Aluminum Bracket
A-370 Mounting Bracket
A-600 R/C Snubber
|
| |
| SUGGESTED SPECIFICATIONS |
| Differential pressure switches
shall incorporate gages and setpoint indicators for continuous
indication of applied pressure and switch settings. Units shall
be diaphragm operated with switching accomplished by phototransistor
controlled (SPDT electro-mechanical relays)(solid state switches).
Setpoint shall be controlled by knobs on front of unit. Switch/gages
shall be Dwyer Instruments, Inc., Series 3000(MR)(MRS) Photohelic
Catalog No. reading to " w.c. in " divisions. SERIES
3000MR(S) |
| |
| Popular Models (Stocked Shown
in Bold): |
| Model
Number |
Range,
Inches W.C. |
Minor
Divs. |
| 3000-0(MR)(MRS) |
0-0.5 |
.01 |
| 3001(MR)(MRS) |
0-1.0 |
.02 |
| 3002(MR)(MRS) |
0-2.0 |
.05 |
| 3003(MR)(MRS) |
0-3.0 |
.10 |
| 3005(MR)(MRS) |
0-5.0 |
.10 |
| 3010(MR)(MRS) |
010 |
.20 |
| 3015(MR)(MRS) |
0-15 |
.50 |
| 3020(MR)(MRS) |
0-20 |
.50 |
| 3030(MR)(MRS) |
0-30 |
1.0 |
| 3050(MR)(MRS) |
0-50 |
1.0 |
| 3100(MR)(MRS) |
0-100 |
2.0 |
| Model
Number |
Range
Pascals |
Minor
Divs |
| 3000(MR)(MRS)-60Pa |
0-60 |
2.0 |
| 3000(MR)(MRS)-125Pa |
0-125 |
5.0 |
| 3000(MR)(MRS)-250Pa |
0-250 |
5.0 |
| 3000(MR)(MRS)-500Pa |
0-500 |
10.0 |
| Model
Number |
Range
Kilopascals |
Minor
Divs |
| 3000(MR)(MRS)-1kPa |
0-1.0 |
.02 |
| 3000(MR)(MRS)-3kPa |
0-3.0 |
.10 |
| 3000(MR)(MRS)-4kPa |
0-4.0 |
.10 |
| Model
Number |
Range
MM W.C. |
Minor
Divs |
| 3000(MR)(MRS)-6MM |
0-6 |
.20 |
| 3000(MR)(MRS)-10MM |
0-10 |
.50 |
| 3000(MR)(MRS)-25MM |
0-25 |
.50 |
| 3000(MR)(MRS)-50MM |
0-50 |
1.0 |
| 3000(MR)(MRS)-100MM |
0-100 |
2.0 |
| Model
Number |
Range
CM W.C. |
Minor
Divs |
| 3000(MR)(MRS)-20CM |
0-20 |
.50 |
When ordering, select either
MR or MRS suffix to Series 3000 number.
Examples: 3001MR or 3001MRS. |
|
|
|
| |
| |
| |
| Previous
Page |
| |
| |