Series HT RH/Temperature
Transmitter |
| Calibration-Free, 2-Wire Design,
Duct or Wall Mount |
| |
Monitor
and control relative
humidity and temperature in building energy management systems
with the Series HT Humidity/Temperature Transmitter. Designed
for demanding HVAC/EMCS applications, the Series HT provides ±3%
RH accuracy and ±1% stability per year. Routine calibration
is not required with the fully interchangeable sensor. Two-wire
connections allow easy instillation directly into air ducts or
within a controlled area. Dimensional Information
|
| |
| SPECIFICATIONS |
Relative Humidity Range: 10 to 90% RH.
Temperature Range: Duct mount: -40 to 140°F (-40 to 60°C), wall
mount: 23 to 131°F (-5 to 55°C).
Accuracy: ±3% RH @ 25°C, ±0.3°C @ 25°C.
Temperature Limits: Duct mount: 14 to 140°F (-10 to 60°C), wall
mount: 23 to 131°F (-5 to 55°C).
Storage Temperature: -40 to 140°F (-40 to 60°C).
Operating Humidity Range: Duct mount: 0 to 100% RH, wall mount: 0 to
90% RH.
Power Requirements: 10 to 28 VDC.
Output Signal: 4 to 20 mA.
Response Time: 15 seconds.
Current Consumption: 4 mA minimum.
Conduit Connection: 1/2" NPT.
Mounting Connection: 3/4" NPT.
Drift: ±2% RH over 2 years.
Temperature Sensor: Pt 1000Ω RTD.
RH Temperature Dependence: <±1.5% RH from 14 to 140°F
(-10 to 60°C).
Temperature Dependence: 0.01°C/°C.
Housing Material: ABS plastic.
Enclosure Rating: Duct mount only IP65.
Weight: 0.6 lb (0.3 kg).
Agency Approvals: CE. |
| |
| ACCESSORIES |
| HT5 - Replacement Sensor. |
| |
| Popular Models: |
| Model
Number |
Input
Sensor |
Supply
Voltage |
| HS-311 |
0-3 V |
110 VAC |
| HS-312 |
0-3 V |
230 VAC |
| HS-111 |
0-1 V |
110 VAC |
| HS-112 |
0-1 V |
230 VAC |
| HS-411 |
4-20 mA |
110 VAC |
| HS-412 |
4-20 mA |
230 VAC |
|
|
|
| |
| Accessories: |
| Model
Number |
Description |
| THC-P |
Humidity Probe, 0 to 3 V Output, 4 ft (1.5 m) Cable |
| TS2-K |
Configuration Key |
|
|
|
| |
| |
| Previous