Series HS Humidity
Switch |
| Programmable, 8 Amp Relay, 3-Digit
Relay |
| |
The
microprocessor based Series
HS Humidity Switch provides control for humidifying or dehumidifying.
Relative humidity, output status, and error messaging can be
viewed on the bright green LED. The switch features 9 user defined
parameters including setpoint, hysteresis, control type, cycle
time, and probe adjustment. Access to programming parameters
can be locked for security purposes using the password protection
feature. Use the configuration key (sold separately) to quickly
program multiple units. The Series HS includes a fitting clip
for panel mounting, gasket, rear terminal cover, and instruction
manual. Dimensional Information
|
| |
| APPLICATIONS |
HS Digital Humidity Switches are suitable for industrial
chillers, environmental chambers, walk-ins and freezers, heat
sealers, beer and wine chillers, mug frosters, coolers, display
cases and cabinets, meat and produce storage, floral preservation,
refrigerated transportation, laboratories, food service equipment,
ovens and dryers, green houses, museums, and tobacco preservation. |
| |
| SPECIFICATIONS |
Relative Humidity Range: 0 to 100% RH.
Input: 0 to 3V humidity probe (not included).
Accuracy: ±1% RH.
Display: 3-digit, green, 1/2" (12.7 mm) digits.
Resolution: 1 digit.
Temperature Limits: 32 to 158°F (0 to 70°C).
Storage Temperature: -4 to 176°F (-20 to 80°C).
Output: 8 A relay @ 250 VAC resistive.
Horsepower Rating (HP): 1/3 HP.
Control Type: ON/OFF.
Power Requirements: 110 VAC or 230 VAC (depending on model).
Memory Backup: Nonvolatile memory.
Weight: 2.3 oz (65 g).
Front Panel Rating: NEMA 4X (IP65).
Agency Approvals: CE, UL. |
| |
|
Description |
Units |
Range |
SP |
Set
Point |
% |
r1
to r2 |
r0 |
Differential
or Hysteresis |
% |
1
to 99 |
r1 |
Lower
Value Set Point |
% |
0
to r2 |
r2 |
Higher
Value Set Point |
% |
r1
to 100 |
d0 |
Control
Type (humidifying/dehumidifying) |
Option |
Hu/dH |
c0 |
Min.
Stop Time for Load |
Minutes |
0
to 59 min. |
c1 |
Continuous
Cycle Time |
Hours |
0
to 24 hr. |
Lc |
RH
Value for 4 ma Input |
% |
0
to 100 |
Hc |
RH
Value for 20 ma Input |
% |
50
to 100 |
P1 |
Probe
Adjustment (shifting) |
% |
0
to 10 |
P2 |
Probe
Type (0-1 V, 0-3 V, 4-20 mA) |
Range |
01/03/42 |
H5 |
Parameter
Access Code |
Numeric |
0
to 99 |
|
|
|
| |
| ACCESSORIES |
| THC-P - Humidity Probe, 0 to 3 V
output, 4 ft (1.5 m) cable. |
| TS2-K - Configuration Key. |
| |
| Popular Models: |
| Model
Number |
Input
Sensor |
Supply
Voltage |
| HS-311 |
0-3 V |
110 VAC |
| HS-312 |
0-3 V |
230 VAC |
| HS-111 |
0-1 V |
110 VAC |
| HS-112 |
0-1 V |
230 VAC |
| HS-411 |
4-20 mA |
110 VAC |
| HS-412 |
4-20 mA |
230 VAC |
|
|
|
| |
| Accessories: |
| Model Number |
Description |
| THC-P |
Humidity Probe, 0 to 3 V Output, 4 ft (1.5 m) Cable |
| TS2-K |
Configuration Key |
|
|
|
| |
| Previous Page |
| |
|