Series HS Humidity Switch

Programmable, 8 Amp Relay, 3-Digit Relay
 

The microprocessor based Series HS Humidity Switch provides control for humidifying or dehumidifying. Relative humidity, output status, and error messaging can be viewed on the bright green LED. The switch features 9 user defined parameters including setpoint, hysteresis, control type, cycle time, and probe adjustment. Access to programming parameters can be locked for security purposes using the password protection feature. Use the configuration key (sold separately) to quickly program multiple units. The Series HS includes a fitting clip for panel mounting, gasket, rear terminal cover, and instruction manual.  Dimensional Information

 
APPLICATIONS

HS Digital Humidity Switches are suitable for industrial chillers, environmental chambers, walk-ins and freezers, heat sealers, beer and wine chillers, mug frosters, coolers, display cases and cabinets, meat and produce storage, floral preservation, refrigerated transportation, laboratories, food service equipment, ovens and dryers, green houses, museums, and tobacco preservation.

 
SPECIFICATIONS
Relative Humidity Range: 0 to 100% RH.
Input: 0 to 3V humidity probe (not included).
Accuracy: ±1% RH.
Display: 3-digit, green, 1/2" (12.7 mm) digits.
Resolution: 1 digit.
Temperature Limits: 32 to 158°F (0 to 70°C).
Storage Temperature: -4 to 176°F (-20 to 80°C).
Output: 8 A relay @ 250 VAC resistive.
Horsepower Rating (HP): 1/3 HP.
Control Type: ON/OFF.
Power Requirements: 110 VAC or 230 VAC (depending on model).
Memory Backup: Nonvolatile memory.
Weight: 2.3 oz (65 g).
Front Panel Rating: NEMA 4X (IP65).
Agency Approvals: CE, UL.
 
 
Description
Units
Range
SP
Set Point
%
r1 to r2
r0
Differential or Hysteresis
%
1 to 99
r1
Lower Value Set Point
%
0 to r2
r2
Higher Value Set Point
%
r1 to 100
d0
Control Type (humidifying/dehumidifying)
Option
Hu/dH
c0
Min. Stop Time for Load
Minutes
0 to 59 min.
c1
Continuous Cycle Time
Hours
0 to 24 hr.
Lc
RH Value for 4 ma Input
%
0 to 100
Hc
RH Value for 20 ma Input
%
50 to 100
P1
Probe Adjustment (shifting)
%
0 to 10
P2
Probe Type (0-1 V, 0-3 V, 4-20 mA)
Range
01/03/42
H5
Parameter Access Code
Numeric
0 to 99
 
ACCESSORIES
THC-P - Humidity Probe, 0 to 3 V output, 4 ft (1.5 m) cable.
TS2-K - Configuration Key.
 
Popular Models:
Model Number Input Sensor Supply Voltage
 HS-311 0-3 V 110 VAC
 HS-312 0-3 V 230 VAC
 HS-111 0-1 V 110 VAC
 HS-112 0-1 V 230 VAC
 HS-411 4-20 mA 110 VAC
 HS-412 4-20 mA 230 VAC
 
Accessories:
Model Number Description
 THC-P Humidity Probe, 0 to 3 V Output, 4 ft (1.5 m) Cable
 TS2-K Configuration Key
 