| Series 4130 and 4150 Temperature Transmitters |

Iso-Verter® II
Transmitters accept thermocouple (4130) or RTD (4151)
inputs, completely isolating them from the output signal
and ground. Output is selectable for your choice of a
linearized 4-20 mA or 0-10 VDC signal. These compact
modules are compatible with industry standard octal bases
for complete interchangeability.

MODEL
CHART (THERMOCOUPLE TRANSMITTERS)

Model
|
Type,
Range
|
Model
|
T/C
Type, Range
|
4130A
4130B
4130C
4130D
4130E
4130F
4130G
4130H
4130J
4130K
|
J,
-100 to 200°C
J, -150 to 200°F
J, 0 to 100°C
J, 0 to 500°F
J, 0 to 250°C
J, 0 to 750°C
J, 0 to 1000°F
K, -150 to 350°F
K, -100 to 200°C
K, 0 to 500°F
|
4130L
4130M
4130N
4130P
4130R
4130S
4130T
4130U
4130W
|
K,
0 to 250°C
K, 0 to 1000°F
K, 0 to 500°C
K, 0 to 2000°F
K, 0 to 1000°C
T, -300 to 250°F
T, -200 to 200°C
T, 0 to 500°F
T, 0 to 250°C
|
PHYSICAL
DATA

| Isolation: |
|
1500
VAC RMS |
| Linearity: |
|
0.1%
of full scale |
| Drift: |
|
±0.02%
per °C typical, ±0.05% per °C
maximum |
| Ambient
Operating Temperature: |
|
32
to 131°F (0 to 55°C) |
| Power
Supply: |
|
85-265
VDC/VAC, 50-400 Hz |
| Output
Loads: |
|
Current:
600 ohms maximum
Voltage: 500 ohms minimum, 20 mA maximum |
| Input
Characteristics: |
|
4130
(Thermocouple): 3 megohms
impedance
4151 (RTD): Search current>500 A |
| Case
Size Including Socket Pins: |
|
2
3/8"W x 3 7/16"H
x 1 ¾"D (60.3 mm W x
87.3mm H x 44.4 mm D. Height
is 2 7/8" (73 mm) above
socket |
MODEL
CHART (RTD TRANSMITTERS)

Model
|
Type,
Range
|
Model
|
Type,
Range
|
4151A
4151B
4151C
4151D
4151E
|
DIN,
-100 to 200°C
DIN, 0 to 100°C
DIN, 0 to 150°C
DIN, 0 to 200°F
DIN, 0 to 200°C
|
4151F
4151G
4151H
4151J
4151K
|
DIN,
0 to 400°F
DIN, 0 to 250°C
DIN, 0 to 500°F
DIN, 0 to 500°C
DIN, 0 to 1000°F
|
|
|
series sc
|

|

|
Eliminate ground
loops, convert signal levels, or interface sensors to
control systems with Series SC Sig-con Signal Conditioners.
Units provide 1800 VDC isolation between input, output,
and power. Easily configure input and output ranges to
fit your application. Zero and span potentiometers allow
50% adjustability of offset and span turn-down within
each of the ranges. Signal conditioners include a diagnostic
LED to indicate input signal status.
PHYSICAL
DATA

| Output: |
|
0
to 5V, 0 to 10V, o 50 a mA,
0 to 20 mA, 4 to 20 mA, configurable |
| Accuracy: |
|
(Includes
linearity & hysteresis)(SC323) ±3.6°F
(±2°C) @ -328 to 1382°F,
Type J, (SC213) ±0.1%, (SC101) ±0.35%
full scale @ 2 mA/<20mV |
| Isolation: |
|
1800
VDC between input, output
and power |
| Stability: |
|
(SC101) ±0.025%/°C,
(SC213) ±0.015%/°C max, (SC323) ±0.04%/°C
max |
| Zero
and Span Adjustment: |
|
50%
of offset and span turn-down
within each range |
| Response
Time: |
|
(SC101 &SC213)
200 msec, (SC323) 500 msec |
| Input
Impedance: |
|
(SC101)
Current: 20 typical,
voltage > 100k ,
(SC323) > 1 M |
| Thermocouple
Burnout Detect: |
|
(SC323)
configurable upscale, downscale,
or disabled |
| Ambient
Operating Temperature: |
|
32
to 131°F (0 to 55°C) |
| Storage
Temperature: |
|
-13
to 158°F (-25 to 70°) |
| Power
Supply: |
|
0
to 30 VDC |
| Power
Consumption: |
|
1.5
W typical, 2.5 W maximum |
| Electrical
Connections: |
|
Screw
terminal for 12-22 AWG |
STOCKED
MODELS

Model
Number
|
Input
Type
|
SC101
|
10
mV to 100 V
DC voltage
input, 1 mA
to 100 mA DC
current input
|
SC213
|
Pt100 ,
Pt500 ,
Pt1000 ,
Cu10, Cu25,
Cu100 RTDs,
3-wire
|
SC323
|
Type
J, K, T, R,
S, E, B Thermocouple
|
|
|
|
|
|
|