Contact Dwyer Sales Department: 1-201-419-6120  |  dwyer@nciweb.com


'); newWindow.document.write('
'); newWindow.document.write('Click screen to close'); newWindow.document.write('
'); newWindow.document.close(); newWindow.focus(); } } //-->
 

Series 8600 Temperature Process Controller

Series 8600 Temperature/Process Controllers are compact and versatile with a choice of horizontal and vertical mount housings.  They set a new standard for quality, ease-of-use and value. While a high level of standard features are included, many function setup items appear in the control menu only when the function is selected, so you don't have to wade through unnecessary items. Units feature a universal input for thermocouple types J, K, E, T, L, N, B, C, S & R; RTD's - 100W Pit. NIST, 100W Pit. DIN, 120W Ni Industrial, 1000W Pit, DIN; differential input (-10 to +10 mV DC) and process input (0 to 20 mA DC, 0 to 10 VDC). A standard 24 volt isolated, regulated power supply is included to operate most standard 4-20 mA transmitters.

Standard features include Self-Tune®, Fuzzy Logic, fully adjustable PID, Auto/Manual control with bumpless transfer and front panel activation key, percent output indication, peak and valley indication, liip break protection and indication. For process inputs, the display is fully programmable from -1999 to +9999 with selectable decimal point location. Most thermocouple and RTD inputs can show shole or tenth degree displays. The Series 8600 is available with single or dual setpoint outputs and can be programmed for on-off, PID or heat/cool or latching alarm. All outputs are isolated form the inputs. Outputs include 10 amp relay, 2.5 amp SSR and 0-20 mA DC (scaleable). 15 VDC SSR drive is standard. Optional dual alarms are fully programmable.
 
See Dimensions
 
Popular Models
Model
Alarm
Output A
Output B
D86010-(1)(0)
D86030-(1)(0)
D86050-(1)(0)
D86110-(1)(0)
D86130-(1)(0)
D86150-(1)(0)
D86111-(1)(0)
D86133-(1)(0)
NO
NO
NO
YES
YES
YES
YES
YES
SSR
RELAY
CURRENT
SSR
RELAY
CURRENT
SSR
RELAY
NONE
NONE
NONE
NONE
NONE
NONE
SSR
RELAY
Note: Specify suffix 1 for horizontal or 0 for vertical mounting.
 
More Standard Features
NEMA 4X (IP 65) Front Panel Resists Dust & Moisture
. Four Password Protested Security Levels
. Front Panel Programmability
. 16 Segments of Ramp/Soak with Program End Control
. Operates on 100-240 VAC, 132-240 VDC
 
PHYSICAL DATA
Front Panel Selectable Inputs:   Thermocouple, RTD, DC voltage or DC current.
Input Impedance:   Thermocouple - 3 megohms minimum
Voltage - 5000 ohms
Current - 10 ohms
RTD Current - 200mA maximum
Display:   Two 4 digit, 7 segment LED; 0.4" (10 mm) high - horizontal models; 0.3" (7.62 mm) high -vertical models
Accuracy:   ±0.25% of span, ±1 least significant digit
Supply Voltage:   100 to 240 VAC nominal, +10%-15%, 50 to 400 Hz, single phase; 132 to 240 VDC +10%-20%
Operating Temperature Range:   14 to 131°F (-10 to 55°C)
Control Output Ratings:   SSR:  2.5 A at 240 VAC resisting at 77°F (25°C). De-rate to 1.25 A at 130°F (55°C)
Relay:  SPDT, 10 A at 240 VAC resistive, ½ hp at 120 VAC, ½ hp at 240 VAC
Alarm Relay:  SPST, 3 A at 240 VAC resistive
Switched Voltage:  15 VDC at 20 mA
Proportional Current:  0-20 mA DC, scaleable into 600 ohms maximum.
Weight:   13 oz. (369 g)
 
SUGGESTED SPECIFICATIONS
Process Controller shall be microprocessor based of 1/8 DIN size with dual four digit LED displays and accuracy of ±0.25% of span, ±1 least significant digit. PID control will Self-Tune® automatically and Fuzzy Logic software shall be included. Selectable inputs and associated impedance to be thermocouple (3 megohms min.), RTD current (200mA max.), current (10 ohms) and voltage (5000 ohms). Sealed front panel shall have NEMA 4X (IP 65) rating. Outputs shall be selectable for relay logic, current, voltage or switched voltage. Electronics replaceable without wiring changes via removable front panel. Process controller shall be Dwyer Model D86 _____.