Contact Dwyer Sales Department: 1-201-419-6120  |  dwyer@nciweb.com


Proximity Series CLS2

Capacitive Level Switch
Powder, Bulk, or Liquids, Auto-Calibration

Proximity Series CLS2The CLS2 is a capacitive technology level switch that does not have any moving parts - no jams, no wear, nothing to break, and no maintenance. State of the art sensing technology in the CLS2, using impulse RF admittance measurement combined with an active guard, provides excellent level measurement and stability while being insensitive to material buildup. This technology also provides immunity to external RF sources like walkie-talkies and cell phones as well as minimal interference with radio communication or other electronic systems.
Capacitive level technology can be used for liquids, powders and bulk materials and is great for difficult applications such as slurries, coating products, and liquids and solids. The CLS2 is ideal for level indication in silos, receivers, and transporters in pneumatic conveying systems. The CLS2 can also be used for liquid interface applications to detect the level of two immiscible liquids that have different dielectric constants such as oil and water. Wetted materials of PVDF and 316 SS assure great chemical compatibility and meet food grade requirements.

Service: Liquids, powder and bulk materials compatible with wetted materials.
Wetted Materials: 316 SS and Kynar® (PVDF).
Temperature Limits: Ambient: -40 to 185°F (-40 to 85°C), -4 to 185°F (-20 to 85°C) with under 24 VAC/DC power supply; Process: -40 to 250°F (-40 to 121°C).
Pressure Limit: 365 psi (25 bar).
Enclosure Rating: Weatherproof, NEMA 4X.
Switch Type: DPDT (two form C).
Electrical Rating: 8A @ 120/240 VAC res., 30 VDC. 1/2 hp @ 120 VAC and 1/4 hp @ 240 VAC ind.
Power Requirements: 12 to 240 VAC/DC.
Power Consumption: 2.8 Watts max.
Electric Connections: 1/2" NPT conduit opening, screw termination and removable terminal block.
Process Connection: See Catalog Page.
Mounting Orientation: Vertical or horizontal.
Set Point Adjustment: Trips when product touches probe. Cut or extend probe to length of desired trip point. Can be cut as short a 1" and can be extended by welding on to probe. (Minimum length will be effected by material being sensed.)
Response Time: 0.2 seconds.
Time Delay: Adjustable, 0 to 60 seconds.
Spark/Static Protection: 10 MEG Ohm dissipation resistance with spark gap. Surge current to 100A max.
Sensitivity: 8 selectable settings, 1, 2, 4, 6, 8, 10, 14, 20 pF (at 30 pF nominal free capacitance).