Contact Dwyer Sales Department: 1-201-419-6120  |  dwyer@nciweb.com


'); newWindow.document.write('
'); newWindow.document.write('Click screen to close'); newWindow.document.write('
'); newWindow.document.close(); newWindow.focus(); } } //-->

Series SLT - Submersible Level Transmitter

316 Stainless Steel Construction, ±0.25% Accuracy, Easy to Install
Series SLT Submersible Level Transmitter is designed to provide accurate and reliable liquid level measurement in tanks, wells, ponds, flood channels, or landfills. The fully submersible transmitter and cable are easy to install-simply lower the unit to the appropriate depth for measurement. The transmitter measures hydrostatic pressure and transmits a 4 to 20 mA output signal proportional to the liquid level. The Series SLT is constructed of 316 stainless steel and includes a removable, non-clogging snub nose end to protect the sensing element. Units are reverse polarity and surge protected. See Dimensions
SPECIFICATIONS

Service: Liquids.
Wetted Parts: 316 stainless steel, Viton O-ring, HDPE cable jacket.
Accuracy: ±0.25% FS, BFSL (includes linearity, hysteresis, and repeatability); ±0.50% FS for model SLT6 only.
Temperature Limits: -40 to 176°F (-40 to 80°C).
Pressure Limits and Overrange Effect: ±0.15% FS @ 300% of maximum range.
Compensated Temperature Range: 32 to 122°F (0 to 50°C).
Thermal Effects: Max ±1% URL output for ±25°C temp. change within compensated range when calibrated @ 25°C.
Power Requirements: 12 to 24 VDC.
Output Signal: 4 to 20 mA DC limited to 30 mA DC.
Zero and Span Adjustments: ±0.50% FS set @ 77°F (25°C).
Loop Resistance: 800O max @ 28V.
Electrical Connection: Attached 4-wire, 20 AWG polyethylene shielded cable.
Weight: 1.0 lb (454 g).
Agency Approvals: CE.

POPULAR MODELS
Model Number Range Cable Length
 SLT6  0 to 6 psi (0 to 13.8 ft water)  50 ft (15 m)
 SLT15  0 to 15 psi (0 to 34.6 ft water)  75 ft (23 m)
 
Previous Page