Example |
CLT
|
V
|
S
|
5
|
F3
|
20.25
|
02.00
|
23.50
|
CLT-VS5F3-20.25-020.00-23.50 |
Construction |
CLT
|
|
|
|
|
|
|
|
Continuous Level Transmitter |
Output |
|
V
C
|
|
|
|
|
|
|
Voltage, proportional signal of 0 to supply voltage |
Stem and Connection Material |
|
|
B
S
|
|
|
|
|
|
Brass with Beryllium copper stops
316 SS with SS ARMCO PH-15-7MO stops |
Connection Type |
|
|
|
1
2
3
4
5
|
|
|
|
|
1/2" NPT (output type V only)
1-1/4" NPT (float F1 only)
2" NPT
3" 150# Flange, carbon steel (connection material S only) (max. press. 150 psi [10.3 bar])
3" 150# Flange, 316 SS (connection material S only) (max. press. 150 psi [10.3 bar]) |
Float Type |
|
|
|
|
|
|
|
|
Material
|
Min. s.g.
|
Max. Press. psi (bar)
|
Float Factor in (mm)
|
|
|
|
|
F1
F2
F3
|
|
|
|
Buna-N
Buna-N
316 SS
|
0.55
0.55
0.75
|
150 (10.3)
150 (10.3)
300 (20.7)
|
2.0 (50.8)
2.5 (63.5)
3.437 (52.4)
|
Indication Length |
|
|
|
|
|
00.00
|
|
|
Length that the unit sends an output for level. Maximum is 68" (173 cm) |
Top Float Stop "C" Dimension |
|
|
|
|
|
|
00.00
|
|
Distance from bottom of mounting connection to upper float stop. Minimum is 1/4" (6.4 mm) |
Overall Length "B" |
|
|
|
|
|
|
|
00.00
|
To calculate overall length, add indication length, top float stop dimension "C", and float factor. Maximum length is 72" (1.82 m) |