The SC448 and SCL448 Strain
Gauge and Bridge Isolators/Transmitters allow low cost
retransmission of any Strain Gauge or Bridge circuit. Featuring
two fixed and two variable excitation supplies, they can isolate
and retransmit to a wide variety of external devices with standard
process signals.
The SC448 operates on line power (85 to 265
V DC or AC, 50 to 400 Hz) so no extra power supply is needed.
The SCL448 operates on low power (9.6 to 28
V DC or AC, 50 to 400 Hz) for systems that work exclusively at
low voltages. Dimensional
Information |
Power Supply
SC448: 85 to 265 VDC/VAC 50 to 400 Hz.
SCL448: 9.6 to 28 VDC/VAC 50 to 400 Hz.
Power Consumption: 2VA.
Isolation: 1800 VAC.
Ambient Temperature Range
Operating: 32 to 131°F (0 to 55°C).
Storage: -40 to 176°F (-40 to 80°C).
Humidity Conditions (non-condensing): 0 to 90% up to 40°C , 10 to
50% at 55°C.
Linearity: 0.1% of span.
Drift: ±0.02% per °C typical, ±0.05% maximum.
Response Time: 2mS, 90% step change.
Input: ±10 mV to ±200 mV, direct or reverse acting.
Input Impedance: >10 Megohms.
Zero Adjustment: 50% of full scale (-25% to +25%).
Span Adjustment: 60% of full scale (-50% to +10%).
Output Ranges: 0 to 1 V, 0.2 to 1 V, 0 to 5 V, 1 to 5 V, 0 to 10 V,
2 to 10 V, 0 to 1 mA, 0.2 to 1 mA, 0 to 5 mA, 1 to 5 mA, 0 to 10 mA, 2 to 10
mA, 0 to 20 mA, 4 to 20 mA.
Current Output Compliance: 12 V.
Maximum Current Output Load: 600 ohms.
Maximum Voltage Output Current (Minimum Voltage Output Load): 20 mA
(500 ohms).
Weight: 4.5 oz (128 g). |