Contact Dwyer Sales Department: 1-201-419-6120  |  dwyer@nciweb.com


'); newWindow.document.write('
'); newWindow.document.write('Click screen to close'); newWindow.document.write('
'); newWindow.document.close(); newWindow.focus(); } } //-->

Series 1400 Analog Setpoint Temperature Controller



Dimensional Enlargement

 
STOCKED MODELS
Model No. Sensor Type Range °F (°C) Output Aux. Alarm
140BM RTD (DIN) On/Off Relay No
141BM 100 Ohm Platinum On/Off Relay Yes
141AM .00385 Ohms/Ohm/°C Time Prop. Relay Yes
140JM 0 to 400 (-20 to 200) Alarm Relay N/A
140BC J Type On/Off Relay No
141BC Thermocouple On/Off Relay Yes
141AC Iron/Constantan Time Prop. Relay Yes
140JC 0 to 800 (-20 to 420) Alarm Relay N/A
140BH K Type On/Off Relay No
141BH Thermocouple On/Off Relay Yes
141AH Chrome/Alumel Time Prop. Relay Yes
140JH 0 to 1600 (-20 to 860) Alarm Relay N/A
 
PHYSICAL DATA
Accuracy: ±2% full scale
Input Impedance: Thermocouple (3 megohms min.) RTD current (500 mA max.) Thermistor current (250 mA max.)
Deviation Indicator: LEDs indicate process value deviation from setpoint of greater than 1.5% full scale.
Thermocouple Break Protection: Upscale standard.
Sensor Break or Short Protection: Standard for RTD or thermistor input.
Supply Voltage: 100 to 240 VAC, 50-400 Hz.
Operating Range: +14 to 130°F (-10 to 55°C); storage -13 to 149°F (-25 to 65°C)
Output Ratings: SSR: 3.5A @ 240 VAC max. @ 25°C typical. Relay (SPST): 3A res., 1.5A ind. @ 250 VAC; Pilot Duty = 250 VA, 2A @ 125 VAC or 1A @ 250 VAC. Current (non-isolated): 4 to 20 mA into 600 ohms max. Logic (non-isolated): 5 VDC @ 25 mA max. Recorder: 0-1 VDC @ 0-1 mA.
Isolation: Relay and SSR outputs are isolated: Current or logic outputs must not share common grounds with the input.
Weight: 8 oz. (227 g)
 
 
 