Questions? Call Us 1-201-419-6111 ext. 21 or sales@nciweb.com

Clark Reliance Model EA100D

The EA100D has been replaced by the EA100G
 
  • EA100DActuate Electric Warning Signals Or Fuel Cut-Out.
  • Pressures To 800 PSI At 520° F
  • FM - Factory Mutual Approved
  • CSA - Canadian Standards Associations (specify when needed)

When tank or boiler levels reach predetermined high or low levels, the Levalarm will actuate bells, horns or lights. EA100D models are also used for fuel cut-out control.  The EA100D can be purchased with or without the body (Model EA100DLB)


Operation: A stainless steel float swings at the end of a pivot rod.  The rod head carries an Alnico V magnet.  The magnet attracts one leg of a U-shaped armature which is  attached to a microswitch leaf actuator.  A buoyed float holds the switch open or closed, depending on terminals used.  As liquid levels fall, the float drops and directs the magnet to the opposite position.  A closed switch actuates alarms.  An open switch achieves fuel cut-out.

EA100DLB
Operation is highly reliable and sensitive because the the magnet counterbalances the float, allowing accurate use of the float's buoyancy.  Note that the magnet does not "slide", thereby eliminating any friction that could impede movement and accuracy.

For high temperature applications, a ventilated housing is available.  Also when insurance or other regulations require two independent fuel cut-outs, two Levalarms may be wired in series.

 

Click to openConvert Your EA100D Float Style Level Alarm Into A Probe Style (Click for EA100DRPT details)

Reliance Retropak KitRetropak Cap Assembly for EA100 Levalarms®

Single and Dual Function Control for Alarms, Pumps & Fuel Cut-Outs
  • Model EA100DRPT Fits EA100 and EA100D

Installs on Boiler, Tanks, Water Columns - Pressures to 800 PSI

  • Designed to retrofit EA100D Models
  • Eliminates the float mechanism
  • Installs without disturbing any boiler piping
  • Higher reliability with conductivity probes
  • Less maintenance
Retrofit Kit Includes:
  1. New flange cover with T probe
  2. Probe housing kit with ½”conduit connection
  3. Replacement flange gasket
  4. One 30 ft. length of 18 gage Teflon® insulated wire are supplied for the installation up to 15 ft. between probe and relay.
    Note: relay control sold separately
Click to openEA100D Cut-a-Way with Spare Parts (Click for Details)
EA100D
 
 
 
Previous Page